INSTRUCTION MANUAL AC8652 REVISION C2000 SeriesFrame Mounted PumpsINSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

Seite 2 - TABLE OF CONTENTS

FIG4. to the o same depth at 90° um and maximum . 5D – SHAFT HUB, SEAL, & SPACER HUB ASSEMBLYUse a spacer bar equal in thicknessgap specified in

Seite 3 - SAFETY INSTRUCTIONS

11 8. Pack the spaces between and around the grid with as much as coupling vendor supplied grease as possible and wipe off the excess until flush wit

Seite 4 - ROTATING COMPONENTS

FinthesuftemtempuforSection.WARNING: Rotating Components Hazard Do not operate pump without all guards in place. Failure to follow these instructions

Seite 5 - PUMP LOCATION

PRIMING AND S RoccuresupersTING TACAUTION: Seal Damage Hazard Do not run pump dry, seal damage may r. Failure to follow these instructions could lt i

Seite 6 - INSTALLATION

5. Remove the O-ring (2-914-stuffing box cover and inspReplace if necessary. IMPELr nut (4-023-0). To do ng the gland (6-014-0) to the stuffing box (

Seite 7

ASSEMBLY PROCEDntosha2. papered edge away from the 3. Place snap ring (5-068-3, flat snap ring) ositioning aring (5- is ve,sinto snap ring groove.

Seite 8 - IN THE SADDLE BRACKET

FIG. 7 “G” Setting Dimensions Shaft Sleeve OD (inches) G(inches) 1.25 1.221.62 1.31 2.0 1.38 7.ith Packed Stuffing Boxes ctor (1-136-0) onto the pump

Seite 9

17 6. Align the pump to the motor as instructed. 7. Connect the pump to the motor. Reinstall the coupling guard and drain plugs. Close drain valve.

Seite 10

ALTERNATE CLAMPING METHOD 18 INTERNAL OR EXTERNAL FLUSHPUMP WITH PACKING (PLUGGED) PUMP WITH PACKING OPTIONAL SEAL CAGE (INTERNAL OR EXTERNAL) PUMP WI

Seite 11

REPAIR PARTS LIST Cat. No. Part Name Quantity Cat. No. Part Name Quantity1-009-0 Shaft Sleeve 1 5-018-4 Bearing Cap, Outboard 1 1-136-0 Deflector

Seite 12

TABLE OF CONTENTS DESCRIPTION...3PUMP APPLICATION...3SAFETY

Seite 13 - SERVICE INSTRUCTIONS

Xylem Inc. 8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379www.xyleminc.com/brands/acfirepumpAC Fire Pump

Seite 14

DESCRIPTION The Series 2000 Frame Mounted Centrifugal Pump is an end suction centerline discharge pump. The Series 2000 Pump’s rear pull out construct

Seite 15 - ASSEMBLY PROCED

WARNINGROTATING COMPONENTSDISCONNECT AND LOCK OUT POWER BEFORE SERVICING. DO NOT OPERATE WITHOUT ALL GUARDS IN PLACE. FIG. 1 WARNINGCAUTIONCONSULT INS

Seite 16 - IMPELLER

PUMP LOCATION Locate the pump so there is sufficient room for inspection, maintenance, and service. If the use of a hoist or tackle is needed, allow a

Seite 17

INSTALLATIONThis pump is built to provide years of service if installed properly and attached to a suitable foundation. A base of concrete weighing 2-

Seite 18 - INTERNAL OR EXTERNAL FLUSH

GROUTING After the pump has been leveled, securely bolted to the floor, and properly aligned, a good grade of non-shrinking grout should be poured ins

Seite 19 - REPAIR PARTS LIST

f. Position the outer guard so it is centered around the shaft, and so there is less than 1/4" of the motor shaft exposed. On guards that utiliz

Seite 20 - DEAL R SER G

Method 2- For Orange Hytrel Insert, 3500 Operation, or All Other Coupler Types Except as Noted Below (See Fig. 5B) a. Make sure each hub is secured t