INSTRUCTION MANUAL S13421 REVISION BFire Pump PackagePumping SystemsINSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
Xylem Inc. 10661 Newkirk Street Dallas, TX 75220 Phone: (469) 221-1200 Fax: (214) 357-5861www.xyleminc.com/brands/bellgossettBell & Gossett is a t
PAGESECTION 1 – GENERALDESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . 1PURPOSE OF MANUAL . . . . . . . . . . . . . . . . . 1SAFETY INST
1SECTION 1 – GENERAL1.1 DESCRIPTIONFire Pump Package systems are custom built tothe requirements provided by the purchaser. TheAC Fire Pump Packag
21.4.3 For periods of storage, the unit should be covered to prevent corrosion and contaminationfrom dirt. It should be stored in a clean, dry loca-t
32.1 LOCATION2.1.1 Locate the pumping system in a clean, well venti-lated and properly drained location. It is recom-mended that the location selecte
43.1 PREPARATION3.1.1 After package is installed and foundation boltsare tightened, check pump alignment. Refer tospecific pump Installation, Operat
3.2.4 PUMP ROTATION, 3 PHASE MOTORS ONLY.Check rotation of electric driven fire pump andjockey pump; refer to appropriate pump, driverand controller
6APPENDIX AGENERAL– FINAL CHECK LIST___ 1. Is the unit base properly leveled, grouted andsecured?___ 2. Are all lubrication points properly lubr
7APPENDIX BELECTRICALWIRING AND CONTROL SETTINGS – FINAL CHECK LIST___ 1. Does the feeder line voltage correspond to theunit voltage? Check the