INSTRUCTION MANUAL
S13421
REVISION B
Fire Pump Package
Pumping Systems
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
Seitenansicht 0
1 2 3 4 5 6 7 8 9 10

Inhaltsverzeichnis

Seite 1

INSTRUCTION MANUAL S13421 REVISION BFire Pump PackagePumping SystemsINSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

Seite 2 - TABLE OF CONTENTS

Xylem Inc. 10661 Newkirk Street Dallas, TX 75220 Phone: (469) 221-1200 Fax: (214) 357-5861www.xyleminc.com/brands/bellgossettBell & Gossett is a t

Seite 3 - SECTION 1 – GENERAL

PAGESECTION 1 – GENERALDESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . 1PURPOSE OF MANUAL . . . . . . . . . . . . . . . . . 1SAFETY INST

Seite 4

1SECTION 1 – GENERAL1.1 DESCRIPTIONFire Pump Package systems are custom built tothe requirements provided by the purchaser. TheAC Fire Pump Packag

Seite 5 - SECTION 2 – INSTALLATION

21.4.3 For periods of storage, the unit should be covered to prevent corrosion and contaminationfrom dirt. It should be stored in a clean, dry loca-t

Seite 6 - SECTION 3 – OPERATION

32.1 LOCATION2.1.1 Locate the pumping system in a clean, well venti-lated and properly drained location. It is recom-mended that the location selecte

Seite 7

43.1 PREPARATION3.1.1 After package is installed and foundation boltsare tightened, check pump alignment. Refer tospecific pump Installation, Operat

Seite 8

3.2.4 PUMP ROTATION, 3 PHASE MOTORS ONLY.Check rotation of electric driven fire pump andjockey pump; refer to appropriate pump, driverand controller

Seite 9 - ELECTRICAL

6APPENDIX AGENERAL– FINAL CHECK LIST___ 1. Is the unit base properly leveled, grouted andsecured?___ 2. Are all lubrication points properly lubr

Seite 10 - Xylem Inc

7APPENDIX BELECTRICALWIRING AND CONTROL SETTINGS – FINAL CHECK LIST___ 1. Does the feeder line voltage correspond to theunit voltage? Check the