INSTRUCTION MANUAL MM-601HSeries FS4-3General PurposeLiquid Flow Switch®
2Maximum Liquid Pressure: 160 psi (11.3 kg/cm2)Liquid Temperature Range (TL): 32 - 300˚F (0 - 149˚C)Ambient Temperature Range (TS): 32 - 120˚F (0 - 49
FLOW RATESSettings will vary when used to sense flow of otherfluids or if located in a vertical pipe.3NOTE: DO NOT USE LIQUID FLOW SWITCHESON SYSTEMS
4Pipe Flow No-FlowSize NPT Maximum Maximumin. (mm) Adjustment Adjustment2 (50) 69.2 50.33 (80) 162.5 143.54 (100) 276.0 241.05 (125) 550.0 440.06 (150
5STEP 2 - Determine the Location of the Flow Switcha. The flow switch must be installed in the pipe using a threaded tee connection or welded fitting
a. Cover Removal and Installation Procedure• Using a flathead screwdriver, loosen but do notremove the two cover screws and remove thecover (A).• Plac
7b. Electrical Conduit Connection• Connect electric conduit to flow switch electrical enclosure.•Follow accepted electrical practices when installing