GB CHATTER NOTIFICATION CONFIGURATION 1303
16
Definition of rules
Rules definition
A rule
measurements or alarms - are processed.
system.
they will be processed by the rule, if not, they will be ignored.
System operate.
Example number one
#
Description
1;
The first element of the rule is 1, thus the data will be processed by the SCADA plug-in
M;
The second element of the rule is M, thus data must come from a Modbus input on any MJK
1;
The third element of the rule is 1, thus data must come from Modbus input number 1 on any
0;
The fourth element of the rule is 0, thus the SCADA plug-in will output the measured value
M;
The fifth element of the rule is M, thus data must come from a measurement.
Example number two
#
Description
1;
The first element of the rule is 1, thus the data will be processed by the SCADA plug-in
M;
The second element of the rule is M, thus data must come from a Modbus input on any MJK
1;
The third element of the rule is 1, thus data must come from Modbus input number 1 on any
1024;
The fourth element of the rule is 1024, thus the SCADA plug-in will output the GSM signal
M;
The fifth element of the rule is M, thus data must come from a measurement.
Definition of rules
Rules are kept in this file:
First element - process where?
The first element is a digit designating which plug-in will process the data coming from this rule:
#1
Description
1;
Data will be treated by the SCADA plug-in