4XXXX REGISTER MAPPING
DRIVE PARAMETERS
Group 1 VFD Signal R/W Set Value (Dec)
40119 Fault Time 1 R —
40120 Fault Time 2 R —
40121 Speed at Flt R —
40122 Freq at Flt R —
40123 Voltage at Flt R —
40124 Current at Flt R —
40125 Status at Flt R —
40126 DI 6-1 At Fault R —
40127 Drive On Time Hi R —
40128 Drive On Time Lo R —
Group 2 VFD Signal R/W Set Value (Dec)
40201 Set Point R —
40202 Actual R —
40203 Pump Speed R —
40204 Wire to Water Power R —
40205 Set Point #1 R —
40206 Set Point #2 R —
40207 Energy Savings R —
40208 Pump Number R
Stopped [0]
Pump 1 [1]
Pump 2 [2]
Pump 3 [3]
Pump 4 [4]
40209 Used Set Point R —
Group 3 VFD Signal R/W Set Value (Hex)
40301 FB CMD Word 1 R —
40302 FB CMD Word 2 R —
40303 FB STS Word 1 R —
40304 FB STS Word 2 R —
40305 Fault Word 1 R —
40306 Fault Word 2 R —
40307 Fault Word 3 R —
40308 Alarm Word 1 R HEX
40309 Alarm Word 2 R HEX
40310 AV Alarm Word R HEX
40311 AV Fault Word R —