29
APPENDIX B: FUSE AND WIRE SIZING
FUSES
Branch circuit protection must be provided by the end
user and sized per national and local electric codes.
The following tables provide fuse recommendations
for short circuit protection on the drive's input power.
The rated fuse currents given in the tables are the
maximums for the mentioned fuse types. If smaller
fuse ratings are used, check that the fuse Arms current
rating is larger than the input current.
Check that the operating time of the fuse is below
0.5 seconds. The operating time depends on the
fuse type, the supply network impedance as well as
the cross-sectional area, material and length of the
supply cable. In case the 0.5 seconds operating time
is exceeded with the gG or T fuses, ultra rapid (aR)
fuses will in most cases reduce the operating time to
an acceptable level.
Input
Voltage
Model
Number
Input
Current
(Arms)
Mains
Fuse Size
(UL Class T)
230V
SPD20400 114 150
SPD20400F 143 200
SPD20400N1 114 150
SPD20500 143 200
SPD20500F 178 250
SPD20500N1 143 200
SPD20600 178 250
SPD20600F 221 300
SPD20600N1 178 250
460V
SPD40400 59 80
SPD40400F 72 90
SPD40400N1 59 80
SPD40500 72 90
SPD40500F 96 125
SPD40500N1 72 90
SPD40600 96 125
SPD40600F 96 125
SPD40600N1 96 125
SPD40750 124 175
SPD40750F 124 175
SPD40750N1 124 175
SPD41000 157 200
SPD41000F 157 200
SPD41000N1 157 200
575V
SPD50400N1 52 60
SPD50500N1 77 100
SPD50600N1 77 100
SPD50750N1 99 150
SPD51000N1 144 200