22-06-2009
Function Requirements: Hardware / Firmware / Software
:
Converter HW Ver.: 807000
Converter FW Ver.: 842009-001
Display HW Ver.: 807055
Display FW Ver.: 841013-012
Texts file Ver.: 841513-010
MJK Field Link Ver.: 840110-035
Function description
:
In the Converter menu of the MagFlux connected to the display, the day Flow data
logger must be started and initialised.
The day Flow is the volume measured by the MagFlux flow meter in 1 day (day
difference)
Minimum 2 (two) days (date shift) must past before any Day Flow values are stored.
Day Flow logger is using the forward counter, it’s not possible to log the reverse or
Sum flow.
The Day Flow value is presented in a csv-file with date and time stamp+ unit.
If the flow totalizer is zero (no flow present during the day), no Day flow is logged for
the day.
The Day Flow is written to the Display logger at midnight (date shift)
In case of Mains power loss the present day, Day flow will not be logged in the
Display logger.
If Bluetooth is used for connection the Display (requires Display PCB HW Ver.:
510251-005 incl. FW Ver.: 841014-009) for downloading the log, the log size is
recommended to 1680 lines. (Setup->display->Graphs->size) This insures a
reasonable transfer time between the Display log and a PC by use of Bluetooth
connection.